GEYA GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

GEYA GRD9L-R Automatic Reclosing RCD Leakage Circuit Breaker User Manual

Model: GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

1. Įvadas

This manual provides essential information for the safe and effective installation, operation, and maintenance of the GEYA GRD9L-R Automatic Reclosing RCD Leakage Circuit Breaker. This device is designed to enhance electrical safety by automatically reclosing when a Residual Current Device (RCD) trips unexpectedly, reducing manual intervention and improving system efficiency. It is suitable for various applications including meter boxes, new energy circuit management, solar PV control boxes, smart electricity systems, smart homes, and charging stations for new energy vehicles.

Prieš įdiegdami ir naudodami, atidžiai perskaitykite šį vadovą ir išsaugokite jį ateičiai.

2. Pagrindinės savybės

  • Automatinis pakartotinis uždarymas: Coupled with a leakage protection circuit breaker (RCD), it automatically recloses when the RCD trips unexpectedly. This eliminates the need for manual reclosing, reduces maintenance costs, and promptly corrects errors to improve efficiency.
  • Integrated Reclosing Attempts: Features 3 integrated reclosing attempts. If continuous reclosing occurs within 15 minutes, an alarm can be sent via an auxiliary contact.
  • Manual/Automatic Selector: Equipped with a manual/automatic selector switch for flexible operation.
  • Dvigubas užrakinimo mechanizmas: Incorporates a double mechanical/electronic locking system for enhanced safety.
  • Priedų suderinamumas: Can be adapted with auxiliary contacts, alarm contacts, shunt releases, and undervoltage releases.
  • Reclosing Time Reset: Reclosing attempt counts are reset if no trip occurs or if a manual reset is performed within 15 minutes of a successful reclosure.

3. Techninės specifikacijos

SpecifikacijaVertė
Modelio numerisGRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
Prekės ženklasGEYA
ttage220 voltų
Dabartinis reitingas63 A (Nominal Current) / 30 mA (Residual Current Sensitivity)
Grandinės pertraukiklio tipasRCD (liekamosios srovės įrenginys)
Lenkų skaičius2
Montavimo tipasWall Mount, Flush Mount
Pakuotės matmenys12 x 11.6 x 9.1 cm
Svoris350 gramų

4. Sąranka ir diegimas

Installation of the GEYA GRD9L-R device should only be performed by a qualified electrician in accordance with local electrical codes and regulations. Ensure the main power supply is disconnected before commencing any installation work.

4.1 Montavimas

The device supports both wall mount and flush mount installations. It is designed to be installed on a DIN rail alongside an RCCB and auxiliary components.

GEYA GRD9L-R installed with auxiliary and RCCB on a DIN rail

4.1 paveikslas: The GRD9L-R device shown installed on a DIN rail with an auxiliary contact module and an RCCB (Residual Current Circuit Breaker). Arrows indicate the direction of installation onto the rail.

Diegimo žingsniai:

  1. Mount the RCCB onto the DIN rail.
  2. Mount the GRD9L-R automatic reclosing device next to the RCCB.
  3. If required, mount the auxiliary contact module next to the GRD9L-R.
  4. Ensure all components are securely fastened to the DIN rail.

4.2 Laidai

Connect the GRD9L-R device according to the provided wiring diagram. Ensure correct polarity and secure terminal connections. The device is designed to be coupled with an RCCB for leakage protection.

Wiring diagram showing GEYA GRD9L-R connected to an alarm lamp and multiple load circuits via an RCCB and MCBs

4.2 paveikslas: Example application wiring diagram. This diagram illustrates how the GRD9L-R (labeled RD) integrates with an alarm lamp, an RCCB, and multiple Miniature Circuit Breakers (MCBs) protecting various loads. Red lines represent live connections, and blue lines represent neutral connections.

Svarbu: Verify all connections before restoring power. Incorrect wiring can lead to malfunction or electrical hazards.

5. Naudojimo instrukcijos

5.1 Manual/Automatic Selector

The GRD9L-R device features a selector switch for choosing between manual and automatic operation modes.

  • AUTOMATINIS režimas: In this mode, the device will automatically attempt to reclose the coupled RCCB after a trip, following the programmed reclosing logic.
  • MANU režimas: In this mode, the automatic reclosing function is disabled. The RCCB must be manually reclosed after a trip.
GEYA GRD9L-R device showing AUTO and MANU selector switch and reclosing logic diagram

5.1 paveikslas: The GEYA GRD9L-R device with its AUTO/MANU selector switch clearly visible. The diagram illustrates the automatic reclosing logic, showing the sequence of ON/OFF states and delay times for the 1st, 2nd, and 3rd trip attempts. It also indicates the PWR (Power) and AUX (Auxiliary) connections.

5.2 Automatic Reclosing Logic

The device attempts to reclose the RCCB up to three times after an unexpected trip. The reclosing intervals are fixed.

Detailed functions diagram of GEYA GRD9L-R showing LED indicators, trip times, and auto mode logic

5.2 paveikslas: Detailed functions diagram for the GRD9L-R. This diagram shows the LED indicators (PWR), trip times (1, 2, 3, 4), and the state of the MCB/RCCB (Auto) over time. It illustrates the reclosing logic with specific delay times (10s, 15min, 60s, 300s) between attempts. The note indicates that if the interval between two closings exceeds 15 minutes, the program clears accumulated closing times. Fixed closing time intervals are 10s, 60s, and 300s.

  • First Trip: After the RCCB trips, the device waits for 10 seconds, then attempts to reclose.
  • Second Trip: If the RCCB trips again within 15 minutes of the first reclosure, the device waits for 60 seconds, then attempts to reclose.
  • Third Trip: If the RCCB trips a third time within 15 minutes of the second reclosure, the device waits for 300 seconds (5 minutes), then attempts to reclose.
  • Užraktas: If the RCCB trips a fourth time, or if reclosure is unsuccessful after the third attempt, the device enters a locked-out state (LOCK) and requires manual intervention.
  • Resetting Attempts: If the interval between two consecutive trips exceeds 15 minutes, the reclosing attempt counter is reset. The counter also resets after a successful reclosure if no further trips occur within 15 minutes, or upon manual reset.

The fixed reclosing time intervals are 10 seconds, 60 seconds, and 300 seconds. For customization of closing times or intervals, please contact GEYA customer support.

5.3 Užrakinimo funkcija

The device includes a locking mechanism for safety during maintenance or inspection. When the lock function is activated, the RCCB cannot be closed, preventing accidental power restoration.

GEYA GRD9L-R device with a padlock inserted into the locking mechanism

5.3 paveikslas: The GRD9L-R device demonstrating the locking function. A padlock is inserted into the designated lock slot, preventing the switch from being moved to the ON position. A note indicates that the RCCB cannot close when the lock function is activated, and the padlock diameter should be less than 3.5 mm.

To activate the locking function, insert a padlock with a shackle diameter less than 3.5 mm into the designated slot on the device. This ensures that the RCCB remains open during circuit checks or maintenance, enhancing safety.

6. Priežiūra

The GEYA GRD9L-R device is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.

  • Vizuali apžiūra: Regularly inspect the device for any signs of physical damage, loose connections, or overheating.
  • Funkcijų testas: Periodically test the RCCB's trip function using its test button. Ensure the GRD9L-R responds by attempting to reclose.
  • Valymas: Įrenginį laikykite švarų, be dulkių ir šiukšlių. Valymui naudokite sausą, minkštą šluostę. Nenaudokite skystų valiklių.
  • Profesionalus patikrinimas: It is recommended to have the electrical system, including the GRD9L-R, inspected by a qualified electrician at least once a year.

Prieš atlikdami bet kokią techninę priežiūrą ar patikrinimą, visada atjunkite maitinimą.

7. Problemų sprendimas

This section provides guidance for common issues. For problems not listed here or if issues persist, contact GEYA customer support.

ProblemaGalima priežastisSprendimas
Device does not reclose after RCCB trip.
  • Device is in MANU mode.
  • Device is in LOCK state (after 3 unsuccessful reclosures).
  • No power to the GRD9L-R device.
  • Fault in the device or wiring.
  • Switch to AUTO mode.
  • Manually reset the RCCB and GRD9L-R. Investigate the persistent fault.
  • Check power supply and connections to the GRD9L-R.
  • Contact qualified personnel for inspection.
Alarm contact activated frequently.
  • Frequent RCCB trips (3 trips within 15 minutes).
  • Persistent electrical fault in the circuit.
  • Investigate and resolve the underlying electrical fault causing the RCCB trips.
  • Kreipkitės į kvalifikuotą elektriką.
RCCB cannot be closed when lock function is active.Padlock is inserted, activating the safety lock.Remove the padlock from the locking slot.

8. Saugos informacija

  • Elektros pavojus: Šis prietaisas veikia esant didelei įtampaitage. Installation, maintenance, and troubleshooting must only be performed by qualified and authorized personnel.
  • Atjunkite maitinimą: Always ensure the main power supply is completely disconnected and locked out before working on the device or associated circuitry.
  • Tinkamas įžeminimas: Ensure all electrical installations are properly grounded according to national and local electrical codes.
  • Aplinkos sąlygos: Nelaikykite įrenginio drėgmės, ekstremalių temperatūrų ar korozinės aplinkos veikiamo.
  • Numatytas naudojimas: Use the device only for its intended purpose as an automatic reclosing mechanism for RCDs. Do not modify the device.

9. Garantija ir palaikymas

GEYA products are manufactured to high-quality standards. For warranty information, please refer to the documentation provided with your purchase or contact your local GEYA distributor. For technical support, inquiries about customization, or service, please visit the official GEYA websvetainėje arba susisiekite su klientų aptarnavimo tarnyba.

Gamintojas: ZHEJIANG GEYA ELECTRICAL CO.,LTD

© 2024 GEYA. Visos teisės saugomos. Šiame vadove pateikta informacija gali būti keičiama be įspėjimo.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.