Tyenaza ETCR2100A+
Tyenaza ETCR2100A+ Digital Clamp Resistance Tester User Manual
Model: ETCR2100A+
1. Įvadas
This manual provides essential instructions for the safe and effective operation of the Tyenaza ETCR2100A+ Digital Clamp Resistance Tester. This device is designed for accurate measurement of grounding resistance and circuit resistance, featuring a dustproof and shockproof structure for reliable performance in various industrial and departmental settings.
Please read this manual thoroughly before using the instrument to ensure proper handling and to prevent damage or injury.

Image 1.1: The Tyenaza ETCR2100A+ Digital Clamp Resistance Tester, showing its overall design with the clamp jaw and control panel.
2. Saugos informacija
Always observe the following safety precautions to avoid electric shock, injury, or damage to the instrument:
- Do not use the instrument if it appears damaged or is operating abnormally.
- Prieš naudodami įsitikinkite, kad baterijų skyrius yra sandariai uždarytas.
- Do not attempt to measure live circuits beyond the specified voltage limits (CAT III 150V).
- Avoid using the instrument in wet environments or during thunderstorms.
- Refer to qualified personnel for any repairs or servicing.
- Keep the instrument away from strong magnetic fields and electric fields exceeding specified limits.
3. Pakuotės turinys
Patikrinkite, ar pakuotėje yra visi reikalingi daiktai:
- 1 x ETCR2100A+ Digital Clamp Atsparumo testeris
- 1 x Accessory (likely a test ring or similar calibration aid)
- 1 x Naudotojo vadovas (šis dokumentas)
- 1x saugojimo dėžė
Note: 1.5V AA batteries (x4) are required and are not included in the package.

Image 3.1: The ETCR2100A+ tester shown with a standard test ring, which is typically included as an accessory for calibration or verification.
4. Produkto ypatybės
The ETCR2100A+ Digital Clamp Resistance Tester offers the following key features:
- Daugiafunkcis ekranas: Resistance and current values are displayed simultaneously on a new black luxury screen.
- Didelis tikslumas: Microprocessor-controlled for precise grounding resistance detection, utilizing fast filtering technology to minimize interference.
- Duomenų valdymas: Features real-time clock, data storage for up to 99 sets, and data retrieval capabilities.
- Garsinis ir vaizdinis signalas: "Beep beep beep" alarm sound with adjustable threshold settings for resistance (1-199 Ω) and current (1-499mA).
- Automatinės funkcijos: Automatic shutdown and fully automatic gear shifting for ease of use.
- Tvirtas dizainas: Shockproof and dustproof structure, suitable for demanding industrial environments.
- Platus pritaikymas: Ideal for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, tower transmission lines, gas stations, factory grounding grids, and lightning rod systems.

4.1 pav.: Stambus planas view of the robust clamp jaws, highlighting the double insulation and structural features designed for durability and safety.
5. Sąranka
5.1 Akumuliatoriaus įdėjimas
The ETCR2100A+ requires four (4) 1.5V AA batteries (not included).
- Locate the battery compartment cover on the back of the instrument.
- Use a suitable tool (if necessary) to open the battery compartment.
- Insert four 1.5V AA batteries, ensuring correct polarity (+/-) as indicated inside the compartment.
- Saugiai uždarykite akumuliatoriaus skyriaus dangtelį.
5.2 Pradinis įjungimas
Įdėjus bateriją, paspauskite ĮJUNGTA/IŠJUNGTA button to power on the device. The LCD display will illuminate, indicating the device is ready for use.
6. Naudojimo instrukcijos
6.1 Pagrindinis matavimas
To perform a grounding resistance test:
- Įsitikinkite, kad prietaisas yra įjungtas.
- Atidarykite klamp žandikaulius paspausdami gaiduką.
- Padėkite klamp around the grounding conductor or circuit to be measured. Ensure the jaws are fully closed around the conductor.
- The resistance value will be displayed on the LCD screen. The device features fully automatic shifting.
- The single measurement time is approximately 0.5 seconds.

Image 6.1: The ETCR2100A+ tester shown clamping an insulated ground wire, demonstrating its capability to accurately test even insulated conductors.
6.2 Single Point Grounding System, Auxiliary Measurement
For single point grounding systems where direct clamp measurement of the lead wire is not feasible, auxiliary methods can be used. The two-point method is illustrated below:

Image 6.2: Diagram showing the two-point method for auxiliary grounding resistance measurement. It depicts a grounding rod (RA) connected to a single point, with a wire extending to a natural grounding point (e.g., water pipe, buried metal) for measurement.
Norėdami naudoti šį metodą:
- Identify a natural grounding point with a low resistance value near the grounding point to be measured. Examples include a water pipe, fire hydrant, or other deeply buried metal structure.
- Connect a wire from the point to be measured to this auxiliary grounding point.
- Clamp the ETCR2100A+ around the connecting wire to perform the measurement.

Image 6.3: The ETCR2100A+ tester positioned in an industrial substation, illustrating a typical application environment for grounding resistance measurement.
6.3 Duomenų saugojimas ir paieška
The instrument can store up to 99 sets of measurement data.
- To store data: After a measurement, press the MEM button to save the current reading.
- To retrieve data: Press the MEM button repeatedly to cycle through stored data.
6.4 Aliarmo funkcija
The ETCR2100A+ features an audible and visual alarm for out-of-range measurements.
- To activate/deactivate the alarm: Press the AL mygtuką.
- To set alarm thresholds: Refer to the device's on-screen menu or specific instructions for setting resistance (1-199 Ω) and current (1-499mA) alarm limits.

Image 6.4: A hand holding the ETCR2100A+ tester, demonstrating its ergonomic design and ease of handling during operation.
7. Priežiūra
7.1 Valymas
Wipe the instrument's exterior with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure the device is powered off before cleaning.
7.2 Saugykla
When not in use for extended periods, remove the batteries to prevent leakage. Store the instrument in its provided storage box in a cool, dry place, away from direct sunlight and extreme temperatures.
7.3 Kalibravimas
Regular calibration by qualified personnel is recommended to maintain measurement accuracy, especially after prolonged use or if accuracy is suspected to be compromised.
8. Problemų sprendimas
| Problema | Galima priežastis | Sprendimas |
|---|---|---|
| Įrenginys neįsijungia. | Neišsikrovusios arba neteisingai įdėtos baterijos. | Pakeiskite baterijas naujomis 1.5 V AA baterijomis, užtikrindami teisingą poliškumą. |
| Netikslūs rodmenys. | Jaws not fully closed; interference from external fields; dirty jaws; need for calibration. | Ensure jaws are fully closed. Move away from strong magnetic/electric fields. Clean jaws. Consider professional calibration. |
| Signalizacija skamba nuolat. | Measurement exceeds set alarm threshold. | Check the measured value against the set alarm limits. Press the AL button to silence or deactivate the alarm. |
| Ekranas tuščias arba mirga. | Low battery power; environmental conditions (extreme temperature/humidity). | Replace batteries. Operate within specified temperature and humidity ranges (-20 ℃ to 55 ℃; 10% RH to 90% RH). |
9. Specifikacijos
| Modelis | ETCR2100A+ |
| Funkcija | Grounding resistance test, circuit resistance test, leakage current test |
| Atsparumo diapazonas | nuo 0.01 Ω iki 200 Ω |
| Pasipriešinimo rezoliucija | 0.001 Ω |
| Dabartinis diapazonas | None (for leakage current test, the range is 1-499mA for alarm setting) |
| Duomenų saugykla | 99 komplektai |
| Alarm Threshold Setting Range (Resistance) | 1-199 Ω |
| Alarm Threshold Setting Range (Current) | 1-499mA |
| Darbinė temperatūra ir drėgmė | -20 ℃ to 55 ℃; 10% RH to 90% RH |
| LCD ekranas | 4 digit LCD digital display |
| Ekrano dydis | Approx. 47 x 28.5mm / 1.85 x 1.12in (L x W) |
| Jaw Size (Round) | Approx. 32mm / 1.26in diameter |
| Jaw Opening Size (Long) | Maždaug 32 mm / 1.26 colio |
| Clamp Size (Long Jaw) | Maždaug 260 x 90 x 56 mm / 10.24 x 3.54 x 2.2 col. |
| Apsaugos lygis | Dviguba izoliacija |
| Struktūriniai ypatumai | Clamp shaped CT |
| Pavarų perjungimas | Fully automatic shifting |
| Išorinis magnetinis laukas | <40A / m |
| Išorinis elektros laukas | <1V/m |
| Vieno matavimo laikas | 0.5 sekundžių |
| Varžos matavimo dažnis | Greater than 1KHz |
| Tested Current Frequency | 50/60Hz automatic |
| Maitinimo šaltinis | 4 x 1.5 V AA baterijos (į komplektą neįeina) |
| Medžiaga | ABS |
| Prekės svoris | 2.13 kilogramo / 4.69 svaro |
10. Garantija ir palaikymas