0063010 vatų

Watts 009M2 Reduced Pressure Zone Backflow Preventer (Model 0063010) Instruction Manual

For Models: 009M2, 009M2-QT

1. Įvadas

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Svarbi saugos informacija

3. Produktas baigtasview ir komponentai

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Sąranka ir diegimas

  1. Patikrinimas prieš montavimą:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Patikrinkite įrenginį, ar nėra kokių nors transportavimo pažeidimų.
    • Ensure all necessary tools and materials for installation are available.
  2. Svetainės paruošimas:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Vamzdžių jungtis:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Patikrinimas po montavimo:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Patikrinkite visas jungtis, ar nėra nuotėkio.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Naudojimo instrukcijos

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Priežiūra

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Problemų sprendimas

ProblemaGalima priežastisSprendimas
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Nėra vandens srauto arba sumažėjęs srautas
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Nuotėkiai iš jungčių
  • Netinkamai užsandarinti sriegiai
  • Pažeistos tarpinės
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Specifikacijos

Modelio numeris0063010 (009M2)
Backflow Preventer TypeSumažinto slėgio zonos mazgas
Korpuso MedžiagaBronza
Inlet/Outlet Connection Size2 Inches (50 MM)
Įleidimo / išleidimo jungties tipasFemale Threaded NPT
Maksimalus darbinis slėgis175 PSI (12.10 barai)
Maksimali temperatūra180 °F (82 °C)
Minimali temperatūra33 °F (0.5 °C)
Apsaugos tipasBackpressure and Backsiphonage
Gaminio matmenys (I x P x A)22 x 10 x 8 colio
Prekės svoris27 svaro
Lead Free StatusNO (For non-potable use only)

9. Garantija ir palaikymas

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts websvetainėje. Naujausias garantijos sąlygas ir nuostatas rasite šiuose šaltiniuose.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Websvetainė: www.watts.com