1. Įvadas ir pabaigaview
The Intermatic ET1125C is a versatile 24-hour electronic time switch designed for precise control of electrical loads. This device offers advanced programming capabilities, including up to 28 events, to-the-minute accuracy, and automatic Daylight Saving Time adjustments. It features a battery backup to maintain programming during power outages and supports a wide input voltage range of 120-277 VAC. The ET1125C is an ideal upgrade from mechanical time switches, providing enhanced functionality and reliability for various applications.
Pagrindinės funkcijos:
- Selector switch for input voltage: 120-277 VAC, 50/60 Hz
- Up to 28 programmable events
- To-the-minute accuracy for precise scheduling
- Temporary or permanent manual override options
- Automatinis vasaros laiko reguliavimas
- Battery backup for program retention during power loss

1 pav.: priekis view of the Intermatic ET1125C with the cover open, revealing the digital display and control buttons.
2. Saugos informacija
WARNING: Risk of Electrical Shock. More than one disconnect switch may be required to de-energize the equipment before servicing. Use 10-18 gauge copper conductors rated for at least 75°C (167°F) for all connections.
Installation and servicing of this electronic time switch should only be performed by qualified personnel in accordance with all national and local electrical codes. Always ensure power is disconnected at the circuit breaker before performing any installation, wiring, or maintenance. Failure to follow these instructions may result in serious injury or death.
- Nenuimkite izoliatoriaus.
- Užtikrinkite tinkamą įžeminimą.
- Patikrinkite ttage settings before applying power.
3. Sąranka ir diegimas
The ET1125C is designed for surface mounting and comes in a Type 1 steel enclosure. Before beginning installation, ensure the mounting location is suitable and all necessary tools and wiring are available.
3.1 Montavimas
Mount the enclosure securely to a flat surface using appropriate fasteners. Ensure the enclosure is level and positioned to allow easy access for wiring and programming.

Figure 2: The Intermatic ET1125C in its Type 1 steel enclosure with the cover closed.
3.2 tomastage Pasirinkimas
The ET1125C features a selector switch to set the input voltage. This switch must be set correctly to match your electrical system's voltage (120V, 208V, 240V, or 277V) before wiring. Refer to the internal diagram for the exact location of this switch.

3 pav. Vidinis view showing the voltage selector switch on the circuit board.
3.3 Laidai
Wiring must be performed by a qualified electrician. The unit supports 2-circuit/30-Amp rating. Connect the incoming power lines (LINE 1, LINE 2) and load lines (LOAD 1, LOAD 2) to the designated terminals. Ensure all connections are secure and comply with local electrical codes. For detailed wiring diagrams, please consult the official installation manual linked in the Support section.
4. Naudojimo instrukcijos
The ET1125C allows for flexible programming and manual control of connected loads.
4.1 Initial Setup and Clock Setting
- After power-up, the display will show the current time and date. If incorrect, press the REŽIMAS button to enter the clock setting mode.
- Naudokite + ir - buttons to adjust the hour, minute, day, month, and year.
- Paspauskite ENTER/KITAS , kad patvirtintumėte kiekvieną nustatymą ir pereitumėte prie kito.
- The unit automatically adjusts for Daylight Saving Time.
4.2 Programming Events
The ET1125C can store up to 28 ON/OFF events. Each event can be set for specific days of the week or daily.
- Paspauskite REŽIMAS button until 'PROGRAM' or 'EVENT' appears on the display.
- Naudokite ENTER/KITAS to cycle through event numbers (e.g., 01 ON, 01 OFF, 02 ON, etc.).
- For each event, use the + ir - buttons to set the desired time and day(s) of the week.
- Specify which load (LOAD 1, LOAD 2, or both) the event applies to using the dedicated ON/OFF buttons for each load during programming.
- Paspauskite ENTER/KITAS to save the event and move to the next.
- To clear an event, navigate to the event and press IŠVALYTI ATMINTĮ.

4 pav. Išsamus view of the LCD display and programming buttons.
4.3 Rankinis nepaisymas
The ET1125C offers both temporary and permanent manual override functions:
- Laikinas nepaisymas: Paspauskite ĮJUNGTA/IŠJUNGTA button for LOAD 1 or LOAD 2. The load will switch state until the next scheduled event, at which point it will resume programmed operation.
- Nuolatinis nepaisymas: Paspauskite ir palaikykite ĮJUNGTA/IŠJUNGTA button for LOAD 1 or LOAD 2 for several seconds until the display indicates 'MANUAL'. The load will remain in its current state, overriding all programmed events, until the manual override is cancelled by pressing the ĮJUNGTA/IŠJUNGTA mygtuką dar kartą.
5. Priežiūra
The Intermatic ET1125C is designed for minimal maintenance. Periodically inspect the enclosure for any signs of damage or corrosion. Ensure the area around the time switch is clean and free from obstructions.
5.1 Akumuliatoriaus keitimas
The unit uses internal batteries to maintain time and program settings during power outages. If the 'LOW BATT' indicator appears on the display, the batteries should be replaced. Refer to the official installation manual for specific battery type and replacement procedures.
6. Problemų sprendimas
If you encounter issues with your ET1125C, consider the following common troubleshooting steps:
- Nėra ekrano / nėra maitinimo: Check the circuit breaker supplying power to the unit. Verify that the voltagPasirinkimo jungiklis yra teisingai nustatytas.
- Apkrova neperjungiama: Ensure the unit is in 'AUTO' mode and not in permanent manual override. Check programmed events for correct times and days. Verify wiring connections.
- Neteisingas laikas / data: Reset the clock as described in Section 4.1. If the issue persists after power outages, the internal batteries may need replacement.
- Programavimo sunkumai: Refer to Section 4.2 for detailed programming steps. Use the IŠVALYTI ATMINTĮ button to reset events if necessary.
For persistent issues or complex problems, contact Intermatic customer support or consult a qualified electrician.
7. Specifikacijos
| Modelio numeris | ET1125C |
| Įvesties tomastage | 120–277 V kintamoji srovė, 50/60 Hz (pasirenkama) |
| Grandinės | 2 grandinių |
| Amp Įvertinimas | 30 Amp |
| Korpuso tipas | NEMA 1 Steel Enclosure |
| Renginių skaičius | Iki 28 |
| Matmenys (G x P x A) | 3.1" x 5.3" x 8" |
| Prekės svoris | 2.8 svaro |
| Medžiaga | Plienas |
| Spalva | Pilka |
| Montavimo tipas | Paviršinis montavimas |
| Perjungti stilių | Mygtuko jungiklis |
| UPC | 078275109957 |
8. Informacija apie garantiją
The Intermatic ET1125C Electronic Time Switch comes with a 1-year limited warranty. This warranty covers replacement of the unit due to manufacturing defects but does not include labor costs associated with removal or reinstallation. For full warranty terms and conditions, please refer to the official documentation or contact Intermatic customer service.
9. Customer Support and Further Information
For detailed installation instructions, wiring diagrams, and advanced programming guides, please refer to the official Installation Manual (PDF):
Download Intermatic ET1125C Installation Manual (PDF)
For additional support, technical assistance, or to inquire about service, please visit the official Intermatic websvetainėje arba susisiekite su klientų aptarnavimo skyriumi.