1. Įvadas

This manual provides essential information for the proper installation, operation, and maintenance of the Notifier FAPT-851 ACCLIMATE Multi-Sensor. The FAPT-851 is an intelligent, addressable multi-sensor designed for use with compatible fire alarm control panels. It combines photoelectric smoke and fixed-temperature heat detection to provide enhanced fire protection and reduce nuisance alarms.

Please read this manual thoroughly before installation and retain it for future reference. Adherence to these instructions is crucial for the reliable performance of the device.

2. Svarbi saugos informacija

Visada laikykitės šių saugos priemonių:

  • Installation and wiring must be performed by qualified personnel in accordance with all national and local codes and regulations.
  • Disconnect all power from the fire alarm control panel before installing or servicing the sensor.
  • Do not paint the sensor. Paint can interfere with proper operation.
  • Test the sensor regularly as described in the Maintenance section.
  • This device is not intended for use in hazardous locations.

3. Pakuotės turinys

Patikrinkite, ar pakuotėje yra visi reikalingi daiktai:

  • Notifier FAPT-851 ACCLIMATE Multi-Sensor
  • Installation and Maintenance Instructions (this document)
Notifier FAPT-851 Multi-Sensor in its retail box

3.1 paveikslas: The Notifier FAPT-851 ACCLIMATE Multi-Sensor packaged in its brown cardboard box. The label on the box clearly displays 'NOTIFIER by Honeywell', 'FAPT-851', 'ACCLIMATE MULTI-SENSOR', and the UPC 0783863021138.

4. Sąranka ir diegimas

4.1 Montavimas

The FAPT-851 sensor is designed for flange mounting. Ensure the mounting location complies with local fire codes and provides optimal coverage.

  1. Select a suitable mounting base (sold separately) compatible with the FAPT-851.
  2. Secure the mounting base to the ceiling or wall using appropriate fasteners.
  3. Align the sensor with the mounting base and rotate clockwise until it clicks into place.

4.2 Laidai

Wiring must be performed according to the fire alarm control panel's installation manual and all applicable codes. The FAPT-851 is an addressable device and requires connection to an intelligent signaling line circuit (SLC).

  • Ensure power to the SLC is disconnected before wiring.
  • Connect the SLC wiring to the terminals on the mounting base as indicated in the base's instructions.
  • Set the sensor's address using the rotary switches on the back of the sensor before mounting it to the base.
Apačia view of the Notifier FAPT-851 Multi-Sensor

4.1 paveikslas: The underside of the Notifier FAPT-851 sensor, showing the rotary address switches and the label with model number, UL listing, and wiring information. This view is critical for setting the device address and understanding connection points.

Notifier FAPT-851 Multi-Sensor and instruction manual in box

4.2 paveikslas: The Notifier FAPT-851 sensor removed from its box, alongside the folded installation and maintenance instructions. This image shows the context of the manual within the product packaging.

5. Naudojimo instrukcijos

5.1 Normalus veikimas

During normal operation, the sensor communicates with the fire alarm control panel. The LED indicator on the sensor will flash periodically (e.g., every few seconds) to indicate normal polling by the control panel. Refer to your control panel's manual for specific LED flash patterns.

5.2 Pavojaus signalas

When the sensor detects smoke or heat exceeding its programmed thresholds, it will enter an alarm state. The LED indicator on the sensor will illuminate steadily (e.g., red) to indicate an alarm condition. The control panel will also register the alarm and activate appropriate notification appliances.

5.3 Trouble Indication

If the sensor experiences a fault or malfunction (e.g., contamination, internal error), it will report a trouble condition to the control panel. The LED indicator may flash in a specific pattern (e.g., amber) or remain off, depending on the nature of the trouble. Consult the control panel's manual for trouble code interpretation.

6. Priežiūra

Regular maintenance ensures the continued reliable operation of your FAPT-851 sensor.

6.1 Valymas

Dust and debris can accumulate on the sensor, potentially affecting its performance. Clean the sensor annually or as needed:

  1. Disconnect power to the fire alarm control panel.
  2. Gently twist the sensor counter-clockwise to remove it from its mounting base.
  3. Use a soft brush or a vacuum cleaner with a soft brush attachment to remove dust from the sensor's vents and chamber.
  4. Išorę nuvalykite šiek tiek damp audinys. Nenaudokite stiprių cheminių medžiagų ar tirpiklių.
  5. Reattach the sensor to its base by aligning and twisting clockwise until it locks.
  6. Restore power to the control panel and verify normal operation.

6.2 Testavimas

Test the sensor after installation and periodically thereafter (e.g., monthly or quarterly, as required by local codes):

  1. Notify appropriate personnel that the fire alarm system will be tested.
  2. Initiate a functional test using approved test methods (e.g., canned smoke for smoke detection, heat gun for heat detection).
  3. Verify that the sensor goes into alarm and the control panel registers the alarm.
  4. Reset the fire alarm control panel.
Notifier FAPT-851 Multi-Sensor with an orange protective cover

6.1 paveikslas: The Notifier FAPT-851 sensor with an orange protective cover installed. This cover is typically used during construction or painting to prevent contamination of the sensor chamber, and must be removed for proper operation.

7. Problemų sprendimas

Dažniausiai pasitaikančias problemas ir galimus jų sprendimus žr. toliau pateiktoje lentelėje.

problemaGalima priežastisSprendimas
Jutiklis nereaguojaIncorrect wiring, incorrect address, power issue, faulty sensor.Check wiring connections, verify sensor address, confirm power to SLC, replace sensor if necessary.
Triukšmo signalizacijaDust/debris in chamber, sensor located in high-smoke/steam area, environmental factors.Clean sensor (Section 6.1), relocate sensor if possible, adjust sensitivity settings on control panel if applicable.
Trouble signal on control panelSensor fault, communication error, contamination.Check control panel for specific trouble code, clean sensor, verify wiring, replace sensor if fault persists.

8. Specifikacijos

Technical specifications for the Notifier FAPT-851 ACCLIMATE Multi-Sensor:

FunkcijaDetalė
Modelio numerisFAPT-851
GamintojasHONEYWELL
MedžiagaMetalas, Plastikas
Montavimo tipasFlanšo tvirtinimas
Matavimo tikslumas±1.5°C (for heat detection)
Pakuotės matmenys4 x 4 x 2 colio
StiliusKlasika

9. Garantija ir palaikymas

For information regarding the product warranty, please refer to the documentation provided with your fire alarm control panel or contact Notifier customer support directly. Notifier provides technical support and resources to assist with installation, operation, and troubleshooting.

For technical assistance or to report issues, please visit the official Notifier website or contact your authorized Notifier distributor.

Susiję dokumentai - FAPT-851

Preview „Notifier DHX-501“ ortakio dūmų detektoriaus įrengimo ir priežiūros vadovas
Šiame vadove pateikiamos išsamios „Notifier DHX-501“ išmaniojo ortakio dūmų detektoriaus korpuso įrengimo, laidų prijungimo, bandymo ir priežiūros procedūros. Jame pateikiami bendri aprašymai, komponentų sąrašai, saugos įspėjimai, nuoseklus įrengimas, periodinė priežiūra ir specifikacijos, skirtos naudoti su „Notifier CPX-551“ ir „SDX-551“ detektoriaus galvutėmis.
Preview FSP-851R Intelligent Photoelectric Smoke Sensor Installation and Maintenance
Installation and maintenance instructions for the FSP-851R Intelligent Photoelectric Smoke Sensor with remote test capability, designed for duct applications. Includes specifications, wiring guides, testing procedures, and cleaning instructions.
Preview NOTIFIER NFS-320C Intelligent Addressable Fire Alarm Control Panel | Datasheet & Features
Explore the NOTIFIER NFS-320C Intelligent Addressable Fire Alarm Control Panel. This datasheet covers its advanced features, ONYX intelligent sensing, FLASHSCAN protocol, network capabilities, and comprehensive device compatibility.
Preview Notifier 30-3003 Explosion-Proof Smoke Detector: Features and Specifications
Discover the features, applications, and technical specifications of the Notifier 30-3003 Explosion-Proof Smoke Detector, designed for hazardous industrial environments.
Preview „Notifier NFS-320“ išmaniosios adresuojamos gaisro signalizacijos sistemos duomenų lapas
Išsamus „Notifier NFS-320“ išmaniosios adresuojamos gaisro signalizacijos sistemos duomenų lapas, kuriame išsamiai aprašytos jos funkcijos, išmaniosios jutimo galimybės, „FlashScan“ protokolas, sistemos specifikacijos, suderinami įrenginiai ir agentūrų patvirtinimai.
Preview Notifier FSP-951 and FSP-951-IV Intelligent Photoelectric Smoke Sensors Installation and Maintenance
This document provides installation and maintenance instructions for Notifier FSP-951 and FSP-951-IV intelligent photoelectric smoke sensors. It details product specifications, wiring guidelines, testing procedures, cleaning methods, and compliance information for fire detection systems.