REFCO 3004145

GOBI II Universal Condensate Pump

Modelis: 3004145

Instrukcijų vadovas

1. Įvadas

The REFCO GOBI II Universal Condensate Pump is designed for efficient and quiet removal of condensate from air conditioning, HVAC, and dehumidifier systems. Suitable for systems ranging from 6,000 BTU/h to 120,000 BTU/h, this pump features a digital water sensor, universal voltage compatibility, and individually configurable flow rates, making it a versatile solution for various applications. This manual provides essential information for safe installation, operation, maintenance, and troubleshooting of your GOBI II pump.

REFCO GOBI II Universal Condensate Pump, assembled view

1.1 pav.: Surinktas view of the GOBI II Universal Condensate Pump.

2. Saugos informacija

Prieš montuodami ir naudodami atidžiai perskaitykite visas saugos instrukcijas. Nesilaikant šių instrukcijų, gali kilti elektros smūgis, gaisras arba sunkūs sužalojimai.

  • Always disconnect power to the air conditioning unit and the pump before performing any installation, maintenance, or troubleshooting.
  • Installation must be performed by a qualified technician in accordance with all local and national electrical and plumbing codes.
  • Ensure the pump is installed in a location where it is protected from direct water spray and extreme temperatures.
  • Do not operate the pump with damaged cables or if it has been dropped or damaged.
  • This pump is designed for condensate water only. Do not use it for other liquids.
  • Keep children and unauthorized persons away from the installation area.

3. Produktas baigtasview

The GOBI II pump system consists of several key components designed for reliable condensate removal.

Diagram showing GOBI II pump components and included accessories

Figure 3.1: GOBI II kit components and labeled diagram.

3.1. Įtraukti komponentai:

  • Maitinimo kabelis
  • Signalizacijos kabelis
  • Star tube and anti-siphon device
  • Varžtai (tvirtinimui)
  • Sraigtiniai inkarai
  • Factory-installed alarm fuse
  • Kabelių ryšiai

3.2. Pagrindinės funkcijos:

  • Universal application for various AC systems.
  • High pumping capacity: 11 GPH (gallons per hour).
  • High discharge head: up to 65.6 ft.
  • Extremely quiet operation: less than 19 dB noise level.
  • Reliable digital water sensor, eliminating traditional float problems.
  • Demand-oriented control for optimized pumping capacity.

4. Sąranka ir diegimas

The GOBI II pump is designed for direct mounting under the air conditioner unit. Follow these steps for proper installation:

  1. Montavimas: Secure the pump's wall back plate (component 9 in Figure 3.1) to a stable surface directly beneath the air conditioning unit using the provided screws and screw anchors. Ensure it is level.
  2. Pump Body Installation: Slide the pump body (component 1 in Figure 3.1) onto the mounted back plate until it clicks securely into place.
  3. Condensate Inlet Connection: Connect the condensate drain line from the air conditioning unit to the pump's inlet. Ensure a tight, leak-free connection.
  4. Išleidimo linijos jungtis: Connect the 1/4" discharge tube from the pump's outlet to your desired drain point. Install the provided anti-siphon device in the discharge line to prevent backflow and ensure proper pump operation. Ensure the discharge line rises vertically for at least 6 inches before running horizontally or downwards.
  5. Elektros jungtis: Connect the power cable to the pump and then to a suitable power supply (100-240 VAC, 50/60 Hz). Ensure all electrical connections are secure and comply with local electrical codes.
  6. Alarm Cable Connection (Optional but Recommended): Connect the alarm cable to the pump's alarm relay terminals and integrate it with your HVAC system's alarm circuit if desired. The alarm relay is interchangeable (NO or NC) and rated for 250VAC, 6.3A or 28VDC, 6.3A.
  7. Testavimas: Once all connections are made, restore power to the system. Pour a small amount of water into the air conditioner's drain pan to verify the pump activates and discharges water correctly. Check for any leaks.

5. Naudojimo instrukcijos

The GOBI II condensate pump operates automatically based on the water level detected by its digital sensor. It will activate when condensate accumulates and shut off once the water is cleared.

5.1. Digital Sensor and Flow Control:

The integrated digital sensor (component 4 in Figure 3.1) precisely monitors the water level, ensuring the pump activates only when necessary. The pump's demand-oriented control adjusts the pumping capacity as needed, optimizing efficiency and minimizing noise.

5.2. Diagnostic LEDs:

The pump features a diagnostic LED (component 8 in Figure 3.1) to indicate its operational status.

Diagram showing diagnostic LEDs: green for normal operation, red for error

Figure 5.1: Diagnostic LED indicators.

  • Žalias šviesos diodas: Indicates normal operation. The pump is powered and functioning correctly.
  • Raudonas šviesos diodas: Indicates an error or alarm condition. Refer to the Troubleshooting section for possible causes.

6. Priežiūra

Regular maintenance ensures the longevity and optimal performance of your GOBI II pump.

  • Mėnesinis patikrinimas: Visually inspect the pump, inlet, and discharge lines for any blockages, kinks, or leaks. Ensure the pump housing is clean.
  • Kasmetinis valymas: Disconnect power to the pump and the AC unit. Carefully remove the pump body from the wall back plate. Clean the water tray (component 5 in Figure 3.1) and the digital sensor (component 4) to remove any sludge, mold, or debris. A soft brush and mild detergent can be used. Rinse thoroughly with clean water.
  • Filtro keitimas: The pump includes a replaceable filter (component 3 in Figure 3.1). Check its condition during annual cleaning and replace if it appears clogged or damaged.
  • Surinkimas: After cleaning, reassemble all components, ensuring they are securely in place. Restore power and test the pump's operation.

7. Problemų sprendimas

If you encounter issues with your GOBI II pump, refer to the following table for common problems and solutions. Always disconnect power before attempting any inspection or repair.

ProblemaGalima priežastisSprendimas
Siurblys neveikiaNo power; Clogged inlet/outlet; Faulty sensor; Motor issueCheck power supply; Clear blockages; Clean digital sensor; Contact support if issue persists.
Siurblys dirba nuolatAnti-siphon device missing/incorrectly installed; Leak in discharge line; Sensor issueInstall/check anti-siphon device; Inspect discharge line for leaks; Clean sensor.
Vandens perpildymasPump not running; Clogged lines; Pump capacity exceeded; Alarm not connectedSee "Pump does not run"; Clear blockages; Ensure system BTU/h is within pump's range; Connect alarm.
Red diagnostic LED is onError condition (e.g., high water alarm, pump fault)Check for blockages, ensure proper installation, and verify power. If the issue persists after checking, contact technical support.

8. Specifikacijos

Detailed technical specifications for the GOBI II Universal Condensate Pump.

ParametrasVertė
Maks. Srauto greitis11 GPH (0.18 galonų per minutę)
Maks. Iškrovimo galvutė65.6 pėdų
Maks. Siurbimo keltuvas10 pėdų
Triukšmo lygis<19 dB(A)
Siurblio tipasDiafragmos tipas
Vamzdžio skersmuo1/4 ″
ttage100 - 240 VAC
Dažnis50/60 Hz
Energijos suvartojimas8 W
Apsaugos klasėI
Signalizacijos relėInterchangeable NO or NC, rated 250VAC, 6.3A or 28VDC, 6.3A
Apsauga nuo patekimoIP44
Kabelio ilgis5 pėdų
Darbinės temperatūros diapazonas5–40 °C (41–104 °F)
Vandens temperatūros diapazonas5–40 °C (41–104 °F)
Laikymo temperatūros diapazonas-4 - 122 °F (-20 - 50 °C)
Prekės svoris2.59 svaro
Pakuotės matmenys13.66 x 12.8 x 2.6 colio

8.1. Capacity Curve:

The following graph illustrates the pump's capacity (flow rate) versus vertical lift/head pressure.

Graph showing GOBI II pump capacity in GPH and l/hr versus vertical lift/head pressure in feet and meters

Figure 8.1: GOBI II Capacity Curve.

9. Garantija

The manufacturer warranty for the GOBI II Universal Condensate Pump begins with the commissioning of the unit. Please refer to the warranty documentation included with your purchase for specific terms and conditions.

10. Parama

For technical assistance, spare parts, or further inquiries, please contact your REFCO product supplier or visit the official REFCO websvetainė, kurioje rasite pagalbos kontaktinę informaciją.

Susiję dokumentai - 3004145

Preview „Gobi II“ kondensato siurblio įrengimo ir naudojimo instrukcija
Išsamus REFCO Gobi II kondensato siurblio vadovas, apimantis ŠVOK/R sistemų įrengimą, eksploatavimą, priežiūrą ir trikčių šalinimą.
Preview REFCO GOBI II kondensato siurblys: trumpas įrengimo vadovas
Oficialus greitas REFCO GOBI II kondensato siurblio (modelis 3004145) vadovas. Pateikiama esminė informacija apie įrengimą, eksploatavimą, saugą ir priežiūrą, siekiant efektyviai pašalinti kondensatą ŠVOK sistemose.
Preview REFCO Gobi II kondensato siurblio įrengimo ir naudojimo instrukcija
Išsamus REFCO Gobi II kondensato siurblio vadovas, kuriame išsamiai aprašomas įrengimas, veikimas, saugos priemonės, techninės specifikacijos ir trikčių šalinimas. Funkcijos: konfigūruojamas tylusis režimas, diagnostinis LED indikatorius, USB jungtis ir platus pritaikymo spektras.
Preview REFCO Combi universalus kondensato siurblys 3004146 Montavimo ir techninis vadovas
Šiame dokumente pateikiama išsami informacija apie REFCO Combi universalaus kondensato siurblio (modelis 3004146) įrengimą, technines specifikacijas, saugos gaires ir trikčių šalinimą.
Preview REFCO VAMP-F Kondensato siurblio trumpasis vadovas
Glaustas REFCO V įrengimo, naudojimo ir priežiūros vadovasAMP-F kondensato siurblys, skirtas efektyviam kondensato šalinimui iš ŠVOK sistemų. Pridedamos techninės specifikacijos ir saugos instrukcijos.
Preview REFCO VAMP-X kondensato siurblio naudojimo instrukcija
Šioje naudojimo instrukcijoje pateikiama išsami informacija apie REFCO VAMP-X kondensato siurblio specifikacijos, įrengimas, eksploatavimas, priežiūra, saugos gairės ir trikčių šalinimas. Pateikiama anglų, vokiečių, prancūzų, italų ir ispanų kalbomis.