Įvadas
This manual provides essential information for the safe and effective installation, operation, and maintenance of your GEYA G2R 2P 63A AC110V Automatic Transfer Switch. Please read this manual thoroughly before installation and use, and retain it for future reference.
Saugos informacija
ĮSPĖJIMAS: Electrical shock hazard. Installation and servicing must be performed by qualified personnel only. Disconnect all power sources before working on the switch.
- Įsitikinkite, kad vardinis tūristage and current of the switch match your application.
- Visada laikykitės vietinių elektros kodeksų ir taisyklių.
- Nenaudokite jungiklio, jei jis atrodo pažeistas.
- The input power supply must be connected in the correct phase sequence.
Produktas baigtasview
The GEYA G2R Automatic Transfer Switch (ATS) is designed to ensure an uninterruptible power supply by automatically switching between a main power source and a backup power source. It features both automatic and manual operation modes and is suitable for DIN rail mounting.
Pagrindinės funkcijos:
- Nominali srovė: 63A
- Įvertintas ttage: AC 110V
- Dviejų režimų veikimas: Automatinis ir rankinis
- Fast Switching: Millisecond-level transfer time (within 50ms)
- Montavimas: DIN Rail and Screw Mounting System
- Medžiaga: High-quality PA6 material with 94V-2 flame retardant grade
Gaminio matmenys:

Vaizdas: Priekinė ir šoninė views of the GEYA G2R Automatic Transfer Switch with detailed dimensions in millimeters. The unit measures 108mm in height, 50.5mm in width (2P version), and 70mm in depth.
Sąranka ir diegimas
The GEYA G2R ATS supports both DIN rail mounting and screw mounting for flexible installation. Ensure the mounting location is dry, well-ventilated, and free from excessive vibration.
Laidų prijungimo instrukcijos:
Refer to the wiring diagram below for correct connection. It is crucial that the input power supply is connected in the correct phase sequence.

Image: Detailed wiring diagram for the GEYA G2R ATS. It illustrates connections for backup power neutral wire (1), common power neutral wire (2), common power supply (3), backup power supply (4), load power (5), load output neutral wire (6), DIN-Rail buckle (7), backup power live wire (8), common power live wire (9), closing indication (10), manual operation handle (11), and load output live wire (12). A note emphasizes correct phase sequence for input power.
ttage pasirinkimas:
Pasirinkite tinkamą tūrįtage model for your system. This model is designed for AC 110V systems. Using an incorrect voltaggali pažeisti valdymo grandinę.

Paveikslėlis: Vol.tage selection guide for GEYA G2R ATS. It shows two configurations: G2R-2P-63A-220V for 220/400V systems or one L line 220V, and G2R-2P-63A-110V for 110/220V systems or one L line 110V. A warning advises choosing the correct voltage to prevent coil damage.
Naudojimo instrukcijos
Veikimo režimai:
- Automatinis režimas: The switch automatically detects power failures in the main source (I) and transfers the load to the backup source (II) within 50 milliseconds. When the main power is restored, it automatically switches back.
- Rankinis režimas: Use the manual operation handle to select and switch between power sources I and II.
Indikatoriaus lemputės būsena:
- When the power supply is under voltage arba overvoltage, the indicator light flashes (flashes every two seconds).
- When the power is cut off, the indicator light goes out.
- Green indicator light constantly on: Main power supply is active.
- Red indicator light constantly on: Backup power supply is active.
Veikimo demonstracinis vaizdo įrašas:
Video: This video demonstrates the operation of the GEYA ATS, showing how to switch between manual and automatic modes, and how the device automatically transfers power when the main supply is interrupted or restored. It illustrates the indicator light behavior during different power states.
Priežiūra
The GEYA G2R ATS is designed for durability with a mechanical life of ≥8000 times and an electrical life of ≥1500 times. Regular maintenance is minimal but important for optimal performance.
- Reguliariai tikrinkite visas laidų jungtis, kad įsitikintumėte, jog jos yra tvirtos ir be korozijos.
- Laikykite įrenginį švarų ir be dulkių ir šiukšlių.
- Test the automatic transfer function periodically by simulating a main power failure (if safe to do so and with appropriate precautions).
Trikčių šalinimas
| Problema | Galima priežastis | Sprendimas |
|---|---|---|
| Switch does not transfer automatically. | Incorrect mode selection (manual instead of auto). Sugedęs maitinimo šaltinis. Control circuit issue. | Ensure the switch is set to "Auto" mode. Check both main and backup power sources. Consult qualified electrician. |
| Neveikia indikacinės lemputės. | Įrenginyje nėra maitinimo. LED gedimas. | Verify power supply connections. Contact support if power is present but lights are off. |
| Overvoltage/Undervoltage indication (flashing light). | Įvesties tūristage outside normal operating range. | Check the stability of your power sources. The unit will automatically recover after 30 seconds if voltage grįžta į normalią būseną. |
Specifikacijos
| Parametras | Vertė |
|---|---|
| Nominali srovė | 63A |
| Nominali izoliacija ttage | 690 V |
| Įvertintas ttage | AC 110V |
| Vardinis dažnis | 50/60Hz |
| Rated Short-Circuit Current | 5KA |
| Mechaninis gyvenimas | ≥8000 kartų |
| Elektrinis gyvenimas | ≥1500 kartų |
| Antipireno klasė | 94V-2 |
| Montavimo tipas | DIN bėgio kalnas |
| Lenkų skaičius | 2 |
| Prekės modelio numeris | IG-G2R-2P-63A-AC110V |
| Pakuotės matmenys | 4.84 x 3.43 x 2.2 colio; 13.44 uncijos |
Garantija ir palaikymas
Dėl garantijos informacijos ar techninės pagalbos kreipkitės į oficialią gamintojo svetainę. websvetainėje arba susisiekite su pirkimo vieta. Išsaugokite pirkimo kvitą garantiniams reikalavimams.
Manufacturer: GEYA
Norėdami gauti daugiau pagalbos, apsilankykite GEYA parduotuvė „Amazon“ platformoje.