MOONS NPSUGMDHB Wireless Node Controller

Specifikacijos
- Customer’s Part Number:
- MOONS’ Part Number: 4696355000211
- Model: NPSUGMDHB
- P/N: A8768
Galimi pakeitimai be įspėjimo
APRAŠYMAI
- The Wireless Node Controllers can be installed in the lighting control box, lamp chamber or installed self-contained under eaves or other sheltered areas due to the solid metal enclosure.
- It is very small size and excellent waterproof.
- It can automatically identify different types of LED driver, such as 0-10V, DALI-2/D4i and DMX(RDM).
- Supports 2 channels 0-10V for color temperature adjustment.
- Supports RGBW color.
- Supports dynamic scenes and animations.
- It communicates with the gateway through a WPAN (Sub-GHz).
- Self-building and self-healing MESH Network.
- The sensor interface supports sensor access with digital and analog outputs.
SAVYBĖS
- Įvesties tūristage:12-30VDC.
- Power consumption: < 1W.
- Wireless communication: IEEE 802.15.4-915MHz.
- Automatically identify dimming mode.
- DMX(RDM) master, up to 6 loads.
- DALI-2/D4i Single-Master Controller, up to 6 loads.
- 2 channels of 0-10V Dimmer, up to 4 loads each channel.
- RGBW color support
- Dynamic scenes and animations
- 1 channel of sensor sample įvestis.
- Save several dimming plans.
- Firmware upgrade: OTA.
- Embedded communication encryption mechanism.
- Radio frequency certification: FCC
- Warranty: 5years.

CHARAKTERISTIKOS
ELEKTROS CHARAKTERISTIKOS
At 20 ℃, 50% RH, 100Kpa conditions.
| Parametras | Bandymo sąlygos | Min | Tip | Maks | Vienetas |
|---|---|---|---|---|---|
| Įvesties tūristage (1) | 12 | 24 | 30 | VDC | |
| Energijos suvartojimas | 0.2 | / | 1.0 | W | |
| Pritemdymas ttage | DA, DB | -6 | / | 22.5 | V |
| DMX voltage | DA, DB to GND | -3.3 | / | +3.3 | V |
| DMX current | DA to DB short | / | / | 70 | mA |
| DMX Baud rate | / | 250 | / | Kbps | |
| DALI BUS voltage | DA to DB | 0 | / | 20.5 | V |
| DALI high level voltage | DA to DB | 9.5 | / | 22.5 | V |
| DALI low level voltage | DA to DB | -6.5 | / | 6.5 | V |
| DALI BUS current | Not transmitting Transmitter sink | 0.5 | / | 2 | mA |
| 0-10 V išėjimo ttage (2) | DA, DB to GND | 0 | / | 11 | V |
| 0-10V current | Kiekvienas kanalas | / | / | 10 | mA |
| Jutiklis Sampskrydistage | 0 | / | 11 | V | |
| WPAN transmission distance | / | / | 300 | m | |
| WPAN band | 904 | / | 926 | MHz | |
| WPAN receiver sensitivity | -100 | / | / | dBm | |
| WPAN transmitter power | / | / | 20.5 | dBm |
Pastaba:
- In the case of DALI-2/D4i mode, the input voltage needs to be higher than the DALI BUS voltage.
- Kai įvesties ttage is 12V, 0-10V can output 10V at most; When the output voltage is > 12V, 0-10V can output 11V.
Eksploatavimo sąlygos
| Parametras | Bandymo sąlygos | Min | Tip | Maks | Vienetas |
|---|---|---|---|---|---|
| Darbinė temperatūra | -40 | / | +70 | °C | |
| Laikymo temperatūra | Dry indoor, well-ventilated place | -40 | / | +85 | °C |
| Santykinė drėgmė | Šalčio nėra | 10 | / | 95 | % |
| Vibracija | / | 1 | / | G | |
| Garantija | 5 | / | / | Metai | |
| Ingress protection classification | Neįdiegta | IP66 | / | / | |
| Degumas | UL94-V0 | / | / |
EMC
| Tipas | Standartinis | Bandymo lygis |
|---|---|---|
| Atsparumas elektrostatinėms iškrovoms | IEC61000-4-2 | 2 lygis |
| RFEMS | IEC61000-4-3 | 2 lygis |
| Electrical fast transient burst immunity | IEC61000-4-4 | 4 lygis |
| Viršįtampis | IEC61000-4-5 | 2 lygis |
| Conducted disturbances induced by RF field immunity | IEC61000-4-6 | 3 lygis |
| Galios dažnio magnetinio lauko atsparumas | IEC61000-4-8 | 3 lygis |
Sertifikavimas
| Tipas | Standartinis |
|---|---|
| Electromagnetic interference characteristics certification | FCC ID: 2BRS4-NPSUGMDHB |
| Energija | FCC 47 CFR Part15 B Class B; FCC 47 CFR Part15 C (915M WPAN); DLC-indoor/outdoor |
| Veiklumas | DALI-2/D4i: IEC62368-PART 101; IEC62368-PART 103; IEC62368-PART 251; IEC62368-PART 252; IEC62368-PART 253; IEC62368-PART 351; (Type D Single-Master Controller) |
Mechaniniai duomenys
Matmenys
Dimensions are provided in the diagrams above.

Antena
Pasirenkami priedai 
ETIKETĖ

Product barcode information:
- The last 8 digits of SN represent the communication address of the product.
- A” indicates that this product operates in the American frequency band;
- The QR code shows the product’s communication address.

Funkcijų aprašymai
Sąsajos
| Vardas | Spalva | Aprašymas |
|---|---|---|
| GALIA | Ruda | Power supply input DC + |
| GND | Juoda | Power supply input DC -; Dimming/sensor Common port |
| SENSORIUS | Mėlyna | Jutiklis sample input + |
| DCOM | Geltona | Dimming/sensor Common port; DMX shielding |
| DA | Violetinė | 0-10V Dimming+ channel 1; DMX data +; DALI bus + |
| DB | Rožinė | 0-10V Dimming+ channel 2; DMX data -; DALI bus – |
| ANTENA | Juoda | Sub-GHz communication antenna interface |
WPAN Module
- Communicate with the Gateway. Transfer various instructions, such as: dimming command, upload power metering data, set parameters and query telemetries accordingly and so on.
- Wireless communication: IEEE 802.15.4-Sub-GHz.
- Embedded communication encryption mechanism.
Pritemdymas
Once the device is powered up, it will automatically identify the dimming mode (DALI-2/D4i / DMX(RDM) /0-10V) of the connected load. After recognition, it will automatically report its own running dimming mode and perform necessary operation in this way.
Pastaba: To achieve perfect recognition of the dimming type, it is recommended that the controller and the LED driver be powered on simultaneously, or the controller be powered on later than the LED driver.
0-10V pritemdymas
- If it is identified as 0-10V dimmer, it can support 2-channel independent 0-10V dimming, which can support adjusting the color temperature (tunable white LED driver and software configuration are required).
- The DIM-TO-OFF LED drivers should be used; the LED drivers’ output will turn off once the dimming voltage yra < 0.5 V.
- Support positive and negative logic dimming (configuration required).
- If each channel is connected to multiple LED drivers, the maximum output current of each channel is 10mA, and if the load current is >10mA, the output voltage will be not accurate.
Pastaba: Kai įvesties ttage is 12V, 0-10V can output 10V at most; When the output voltage is > 12V, 0-10V can output 11V.
DMX(RDM)
- If identified as a DMX(RDM) master, it can support up to 6 loads (maximum 3 slots for each load) and can be automatically addressed to support RDM instructions.
- 4 loads are recommended.

DALI-2/D4i
- If identified as a DALI-2/D4i Single-Master Controller, up to 6 loads (one address for each load) can be supported, supporting IEC62386-101/103/251/252/253/351 (TYPE D).
- 4 loads are recommended.
Pastaba:
- At least one of the DALI-2/D4i LED drivers needs to be set to supply power to the DALI bus.
- Maximum of 6 DALI-2/D4i LED Drivers, any DALI-2/D4i LED Drivers >4 will need the power supply disabled
- In the case of DALI-2/D4i mode, the input voltage needs to be higher than the DALI BUS voltage.
Jutiklio įvestis
- 1 channel of sensor input interface.
- Sensors with 0-10V output can be accessed.
- Passive digital output can be accessed.
- Sensors must be configured in software before it is functional in system.
Indikacinės lemputės
| Spalva | Būsena | Nurodykite |
|---|---|---|
| RAUDONA | IŠJUNGTA | Nėra galios |
| RAUDONA | ON | Initial process or some failure/error happened |
| RAUDONA | Blykstė | Trying to identify the dimming |
Pastaba:
- Purple light indicates that the communication between node controller and LED driver is lost. This might be due to use wrong LED driver or LED driver is not power on or wiring error (for example the reverse connection of the DMX bus). Please check the wiring connection or the power-on status of the LED driver, and then re-power the node controller.
MONTAVIMAS
For DALI-2/D4i applications with sensor 
For DMX(RDM) applications with sensor 
For 0-10V Dim to off applications with sensor 
For 0-10V Tunable white applications with sensor 
Recommended installation of antenna interface 
Recommended installation of M18 Antenna 
UŽSAKYMAS
| APRAŠYMAS | UŽSAKYMO KODAS |
| NPSUGMDHB3in1 Wireless Node Controller (without Antenna) | 4696355000211 |
| Straight Whip Antenna(RP-SMA connect) | 4741135000149(Optional accessories) |
| Right Angle Whip Antenna(RP-SMA connect) | 4741135000150(Optional accessories) |
| M18 Antenna(RP-SMA connect) | 4741135000153(Optional accessories) |
FCC pareiškimas
Šis įrenginys atitinka FCC taisyklių 15 dalį. Eksploatacijai taikomos dvi sąlygos:
- Šis prietaisas negali sukelti žalingų trukdžių ir
- Šis įrenginys turi priimti bet kokius gaunamus trikdžius, įskaitant trikdžius, kurie gali sukelti nepageidaujamą veikimą.
Atsargiai: Vartotojas įspėjamas, kad pakeitimai ar modifikacijos, kurių aiškiai nepatvirtino už atitiktį atsakinga šalis, gali panaikinti vartotojo teisę naudoti įrangą.
Pastaba: Ši įranga buvo išbandyta ir nustatyta, kad ji atitinka B klasės skaitmeninio įrenginio apribojimus pagal FCC taisyklių 15 dalį.
Šios ribos sukurtos siekiant užtikrinti pagrįstą apsaugą nuo žalingų trukdžių įrengiant gyvenamosiose patalpose. Ši įranga generuoja ir gali skleisti radijo dažnio energiją ir, jei ji sumontuota ir naudojama ne pagal instrukcijas, gali sukelti žalingų radijo ryšio trikdžių. Tačiau nėra garantijos, kad tam tikrame įrengime nebus trikdžių. Jei ši įranga sukelia žalingus radijo ar televizijos signalų priėmimo trikdžius, kuriuos galima nustatyti išjungiant ir įjungiant įrangą, naudotojas raginamas pabandyti ištaisyti trikdžius viena ar keliomis iš šių priemonių:
- Perkelkite arba perkelkite priėmimo anteną.
- Padidinkite atstumą tarp įrangos ir imtuvo.
- Įjunkite įrangą į kitokios grandinės lizdą nei imtuvas.
- Dėl pagalbos kreipkitės į pardavėją arba patyrusį radijo/televizijos techniką.
Kad būtų laikomasi FCC radijo dažnio poveikio gairių, ši įranga turi būti sumontuota ir eksploatuojama mažiausiai 20 cm atstumu nuo radiatoriaus ir kūno: Naudokite tik pateiktą anteną.
CUSTOMER’S APPROVAL STAMP
Please sign back after your approval. The specifications will come into force when we receive purchase order.
| DWG. | CHK. | STANDARTAS | APPD. |
Galimi pakeitimai be įspėjimo
© 2024 MOONS’. All rights reserved. All content contained herein is subject to change without prior notice. More product documentation and MOONS’ terms and conditions are available at https://www.moonsindustries.com
History Version
| Rev. | Data | Turinys | EKO Nr. | DWG. | CHK. | APR. |
| A0 | 2025-09-15 | Pirmoji versija | Jiabin.gu | Wanghui.yan | Yiping.lai | |
| A1 | 2025-11-14 | Change the model; modify the antenna;modify the label. | ECO25-1265DE | Jiabin.gu | Wanghui.yan | Yiping.lai |
| A2 | 2026-01-13 | Correct the line lengths in the mechanical drawings | ECO26-0037DE | Jiabin.gu | Jackie.gu | Yiping.lai |
Dokumentai / Ištekliai
![]() | NPSUGMDHB Wireless Node Controller |
Nuorodos
- Jackie.gujackie.gu
- Jiabin.gujiabin.gu
- moonsindustries.comwww.moonsindustries.com
- Vartotojo vadovasmanual.tools